Τίτλος: Energy upgrading of buildings. A holistic approach for the Natural History Museum of Crete, Greece
Συγγραφείς: Al Katsaprakakis, Dimitris 
Georgila, Klairi 
Zidianakis, Georgios 
Michopoulos, Apostolos 
Psarras, Nikolaos 
Christakis, Dimitris G. 
Condaxakis, Constantinos 
Kanouras, Spyros 
Major Field of Science: Engineering and Technology
Field Category: Materials Engineering
Λέξεις-κλειδιά: Buildings energy saving upgrade;Small wind turbines;Photovoltaic stations on roofs;Open loop normal geothermal systems;Heating and cooling loads;Bioclimatic measures for outdoor spaces
Ημερομηνία Έκδοσης: Δεκ-2017
Πηγή: Renewable Energy, 2017, vol. 114, pp.1306-1332
Volume: 114
Start page: 1306
End page: 1332
Περιοδικό: Renewable Energy 
Περίληψη: This article presents the fundamental points of the accomplished work regarding the energy upgrading of the building of the Natural History Museum of Crete, Greece, based on a cluster of passive and active measures. The main target was the building's energy efficiency upgrading from D to A+ rank. Among the passive measures, insulation of the building's envelope, installation of new windows and doors, construction of a green roof and planting of an outdoor space at the south side of the building to improve the ambient climate locally are included. Furthermore, small wind turbines and a photovoltaic station on the roof, geothermal heat pumps with an open loop system operating with seawater, new lighting equipment controlled by a central management system and reactive power coefficient compensation constitute the proposed active systems. Energy saving percentages from 40% to 93% are achieved with all the proposed technologies. In total, the primary energy specific consumption is reduced from 273.65 kWh/m(2) at 18.36 kWh/m(2), giving a total energy saving percentage of 93.29%. The building's energy efficiency is upgraded from the rank D to the rank A+, according to the European Union's standards. The total cost of the proposed measures is estimated approximately at 900,000.
URI: https://hdl.handle.net/20.500.14279/10496
ISSN: 09601481
DOI: 10.1016/j.renene.2017.08.021
Rights: © Elsevier
Type: Article
Affiliation: Cyprus University of Technology 
Hellenic Mediterranean University 
University of Crete 
AID Engineering LTD 
Diopsis Consulting Ltd 
Publication Type: Peer Reviewed
Εμφανίζεται στις συλλογές:Άρθρα/Articles

CORE Recommender
Δείξε την πλήρη περιγραφή του τεκμηρίου

SCOPUSTM   
Citations

24
checked on 9 Νοε 2023

WEB OF SCIENCETM
Citations 20

20
Last Week
0
Last month
0
checked on 29 Οκτ 2023

Page view(s)

448
Last Week
1
Last month
1
checked on 27 Δεκ 2024

Google ScholarTM

Check

Altmetric


Όλα τα τεκμήρια του δικτυακού τόπου προστατεύονται από πνευματικά δικαιώματα