Παρακαλώ χρησιμοποιήστε αυτό το αναγνωριστικό για να παραπέμψετε ή να δημιουργήσετε σύνδεσμο προς αυτό το τεκμήριο: https://hdl.handle.net/20.500.14279/9056
Τίτλος: Evaluation of ground source heat pump systems for residential buildings in warm Mediterranean regions: the example of Cyprus
Συγγραφείς: Michopoulos, Apostolos 
Voulgari, Vasiliki 
Tsikaloudaki, Katerina 
Zachariadis, Theodoros 
metadata.dc.contributor.other: Μιχόπουλος, Απόστολος
Βούλγαρη, Βασιλική
Ζαχαριάδης, Θεόδωρος
Major Field of Science: Engineering and Technology
Field Category: Mechanical Engineering
Λέξεις-κλειδιά: CO2 emissions;Economic analysis;Energy analysis;Ground source heat pump;Residential buildings
Ημερομηνία Έκδοσης: 18-Φεβ-2016
Πηγή: Energy Efficiency, 2016, vol. 9, no. 6, pp. 1421-1436
Volume: 9
Issue: 6
Start page: 1421
End page: 1436
Περιοδικό: Energy Efficiency 
Περίληψη: This paper presents a feasibility analysis for the installation of ground source heat pump systems in Cyprus. Two reference buildings, a single- and a multi-family one, are designed and analyzed using the EnergyPlus software, in order to calculate their energy needs for heating and cooling for the climate conditions of Cyprus, one of the warmest areas in Southern Europe. These energy needs are assumed to be covered by the conventional heating and cooling systems that are most widely used in Cyprus or alternatively by a ground source heat pump system, which consists of a vertical ground heat exchanger and water-to-water heat pumps and is analyzed using an in-house developed and validated code. Primary energy consumption and the resulting CO2 emissions for both the conventional and the alternative systems are calculated and compared. Results show that the installation of the ground source heat pump system achieves in most cases substantial reductions in primary energy use for both types of buildings. As regards carbon emissions, the findings are less clear: Emissions of the geothermal system are higher than those of the conventional system for the single-family building but considerably lower for the multi-family one. From an economic perspective, the geothermal system compares favorably with the conventional systems in many cases, particularly for the multi-family building.
URI: https://hdl.handle.net/20.500.14279/9056
ISSN: 15706478
DOI: 10.1007/s12053-016-9431-1
Rights: © Springer Nature
Type: Article
Affiliation: Cyprus University of Technology 
Aristotle University of Thessaloniki 
Publication Type: Peer Reviewed
Εμφανίζεται στις συλλογές:Άρθρα/Articles

Αρχεία σε αυτό το τεκμήριο:
Αρχείο Περιγραφή ΜέγεθοςΜορφότυπος
Zachariades.pdfCan archive pre-print and post-print or publisher's version/PDF1.38 MBAdobe PDFΔείτε/ Ανοίξτε
CORE Recommender
Δείξε την πλήρη περιγραφή του τεκμηρίου

SCOPUSTM   
Citations

25
checked on 9 Νοε 2023

WEB OF SCIENCETM
Citations

19
Last Week
0
Last month
0
checked on 29 Οκτ 2023

Page view(s) 10

555
Last Week
0
Last month
7
checked on 22 Νοε 2024

Download(s) 5

1.025
checked on 22 Νοε 2024

Google ScholarTM

Check

Altmetric


Όλα τα τεκμήρια του δικτυακού τόπου προστατεύονται από πνευματικά δικαιώματα