Παρακαλώ χρησιμοποιήστε αυτό το αναγνωριστικό για να παραπέμψετε ή να δημιουργήσετε σύνδεσμο προς αυτό το τεκμήριο:
https://hdl.handle.net/20.500.14279/30667
Τίτλος: | Power cable simulation of failure through temperature monitoring of optical fibres with a state-of-the-art distributed sensing instrument | Συγγραφείς: | Ioannou, Andreas Metaxas, Andreas Argyrou, Maria C. Kouzoupou, Charalambos Kalli, Kyriacos Chatzis, Sotirios P. Panaretou, Georgios Marchesini, Pierpaolo Mondanos, Michael Karaulanov, Rumen Agathocleous, Michalis Dionysiou, Antreas Stavrakis, Efstathios Nicolaou, Nicolas |
Editors: | Wuilpart, Marc Caucheteur, Christophe |
Major Field of Science: | Engineering and Technology | Field Category: | Electrical Engineering - Electronic Engineering - Information Engineering | Λέξεις-κλειδιά: | Distributed sensing;optical fibers | Ημερομηνία Έκδοσης: | 23-Μαΐ-2023 | Πηγή: | 2023 European Workshop on Optical Fibre Sensors, EWOFS 2023, Mons, Belgium, 23 - 26 May 2023through 26 May 2023 | Volume: | 12643 | Conference: | Proceedings of SPIE - The International Society for Optical Engineering | Περίληψη: | In this work we utilize multimode optical fibers for the detection of simulated errors or failures in underground power cables. It is known that in cases of failure the underground transmission cables overheat locally, they become a hot-spot, and it is extremely difficult to detect and locate the problem. The proposed methodology is as follows, having an underground electric cable we simulate various temperature profiles whilst the optical fiber was placed in selected distances away from our simulated fault to examine the detection performance of our fiber. In this way we aim to stabilize the operation of the underground cable damage detection system that is placed by the Electricity Authority of Cyprus. The EAC has certain locations where the existing single-mode optical fibres are collocated with the underground power cables, although relative spacing may not be constant. Our data will give an indication of how important is uniform spacing between power and optical cables. We examine if any change in the temperature of the power cable is also reflected in the optical fibre cable. The real-time and continuous monitoring of the temperature of the optical cables through the distributed sensing systems may help identifying abnormal cable behaviour (hot spots) and possible future network failures in the power network. | URI: | https://hdl.handle.net/20.500.14279/30667 | ISBN: | 9781510665002 | ISSN: | 0277786X | DOI: | 10.1117/12.2678087 | Rights: | © SPIE Attribution-NonCommercial-NoDerivatives 4.0 International |
Type: | Conference Papers | Affiliation: | Cyprus University of Technology Statistical Machine Learning Laboratory Silixa Resoloupe Algolysis |
Εμφανίζεται στις συλλογές: | Δημοσιεύσεις σε συνέδρια /Conference papers or poster or presentation |
CORE Recommender
Αυτό το τεκμήριο προστατεύεται από άδεια Άδεια Creative Commons