Περίληψη: This paper proposes a wide-area backup protection (WABP) method for transmission systems using sparse synchronized/unsynchronized PMU measurements. The method is aimed at addressing practical challenges such as temporary loss of the time-synchronization signal (LTSS), sparse PMU coverage, and communication failures and latencies. A linear and computationally efficient formulation is proposed to identify the faulted line in near real-time based on the superimposed-circuit concept. An index is proposed that quantifies the mismatch degrees between the expected and observed superimposed phasors without requiring full network observability. The method can work well with unsynchronized measurements without imposing a significant computational burden. This is achieved by canceling out the effect of angle drifts caused by LTSS from the equations. Since no matrix inversion is involved, sparse PMU measurements do not result in singularity, and thus, the unsolvability of the equations. A technique is proposed to assess the feasibility of faulted-line identification by a given set of PMUs. Being robust against measurement and parameter errors, the method performs well with PMUs of different reporting rates regardless of the fault distance, type, and resistance. More than 200,000 simulations conducted on the IEEE 39-bus test system verify the effectiveness of the proposed WABP method.
URI: https://hdl.handle.net/20.500.14279/29940
ISSN: 08858977
DOI: 10.1109/TPWRD.2023.3249822
Rights: © Copyright IEEE - All rights reserved.
Type: Article
Affiliation: University of Leeds 
Cyprus University of Technology 
Schweitzer Engineering Laboratories 
Εμφανίζεται στις συλλογές:Άρθρα/Articles

CORE Recommender
Δείξε την πλήρη περιγραφή του τεκμηρίου

SCOPUSTM   
Citations

3
checked on 14 Μαρ 2024

Page view(s)

144
Last Week
0
Last month
17
checked on 19 Μαϊ 2024

Google ScholarTM

Check

Altmetric


Αυτό το τεκμήριο προστατεύεται από άδεια Άδεια Creative Commons Creative Commons