Παρακαλώ χρησιμοποιήστε αυτό το αναγνωριστικό για να παραπέμψετε ή να δημιουργήσετε σύνδεσμο προς αυτό το τεκμήριο: https://hdl.handle.net/20.500.14279/18276
Τίτλος: Stochastic Unit Commitment in Low-Inertia Grids
Συγγραφείς: Paturet, Matthieu 
Markovic, Uros 
Delikaraoglou, Stefanos 
Vrettos, Evangelos 
Aristidou, Petros 
Hug, Gabriela 
Major Field of Science: Engineering and Technology
Field Category: Electrical Engineering - Electronic Engineering - Information Engineering
Λέξεις-κλειδιά: Unit commitment;Low-inertia grid;Frequency constraints;Wind uncertainty;Voltage source converter
Ημερομηνία Έκδοσης: Σεπ-2020
Πηγή: IEEE Transactions on Power Systems, 2020, vol. 35, no. 5, pp. 3448 - 3458
Volume: 35
Issue: 5
Start page: 3448
End page: 3458
Περιοδικό: IEEE Transactions on Power Systems 
Περίληψη: In this paper, the Unit Commitment (UC) problem in a power network with low levels of rotational inertia is studied. Frequency-related constraints, namely the limitation on Rate-of-Change-of-Frequency (RoCoF), frequency nadir and steady-state frequency error, are derived from a uniform system frequency response model that incorporates dynamics and controls of both synchronous generators and grid-forming inverters. These constraints are then included into a stochastic UC formulation that accounts for wind power and equipment contingency uncertainties using a scenario-tree approach. In contrast to the linear RoCoF and steady-state frequency error constraints, the nadir constraint is highly nonlinear. To preserve the mixed-integer linear formulation of the stochastic UC model, we propose a computationally efficient approach that allows to recast the nadir constraint by introducing appropriate bounds on relevant decision variables of the UC model. This method is shown to be generally more accurate and computationally more efficient for medium-sized networks than a piece-wise linearization method adapted from the literature. Simulation results for a modified IEEE RTS-96 system revealed that the inclusion of inertia-related constraints significantly influences the UC decisions and increases total costs, as more synchronous machines are forced to be online to provide inertial response.
ISSN: 08858950
DOI: 10.1109/tpwrs.2020.2987076
Rights: © IEEE
Type: Article
Affiliation: Cyprus University of Technology 
ETH Zurich 
Institute of Harvard and MIT 
Publication Type: Peer Reviewed
Εμφανίζεται στις συλλογές:Άρθρα/Articles

Αρχεία σε αυτό το τεκμήριο:
Αρχείο Περιγραφή ΜέγεθοςΜορφότυπος
manuscript.pdf8.45 MBAdobe PDFΔείτε/ Ανοίξτε
CORE Recommender
Δείξε την πλήρη περιγραφή του τεκμηρίου

SCOPUSTM   
Citations

2
checked on 21 Μαρ 2021

WEB OF SCIENCETM
Citations

59
Last Week
1
Last month
1
checked on 29 Οκτ 2023

Page view(s) 50

356
Last Week
0
Last month
1
checked on 22 Δεκ 2024

Download(s)

234
checked on 22 Δεκ 2024

Google ScholarTM

Check

Altmetric


Όλα τα τεκμήρια του δικτυακού τόπου προστατεύονται από πνευματικά δικαιώματα